1 Scope
This document describes several test methods for measuring the ammonia amount fraction
in natural gas and biomethane at the trace level (µmol mol-1). The suitable handling and sampling of pressurised mixtures of ammonia in methane
that are applied to several different ammonia measurement systems are described. The measurement systems are comprised of readily available commercial spectroscopic analysers that are specific
to ammonia. These NH3 analysers are considered as a black box in terms of their operation, which is dependent
on the instructions of the manufacturer. The document describes suitable calibration
and measurement strategies to quantify ammonia in (bio)methane around and above the
10 mg m-3 (14 µmol mol-1) level and applies to analysis within absolute pressure ranges of 1 bar – 2 bar,
temperatures of 0 °C – 40 °C and relative humidity <90 %.
References are also made to additional standards that are applied either to natural
gas analysis or air quality measurements. In this document the matrix gas is always
methane or biomethane and the measurand is the amount fraction NH3.
NOTE 1 bar = 0,1 MPa =105 Pa; 1 MPa = 1 N/mm2.