1 Scope
This document is applicable to air conditioners, heat pumps and liquid chilling packages,
including comfort and process chillers. It applies to factory made units defined in
EN 14511‑1, except single duct, double duct, control cabinet and close control units. It also
covers direct exchange-to-water(brine) heat pumps (DX-to-water(brine)) as defined
in EN 15879‑1.
This document also applies to hybrid units as defined in this standard.
This document specifies the temperatures, part load conditions and the calculation
methods for the determination of seasonal energy efficiency SEER and SEERon, seasonal space cooling energy efficiencyηs,c, seasonal coefficient of performanceSCOP, SCOPon and SCOPnet, seasonal space heating energy efficiencyηs,h and seasonal energy performance ratioSEPR.
Such calculation methods can be based on calculated or measured values.
In case of measured values, this document specifies the test methods for determination
of capacities, EER and COP values during active mode at part load conditions. It also establishes test methods for power input during
thermostat-off mode, standby mode, off mode and crankcase heater mode.
NOTE 1 The word “unit” is used instead of the full terms of the products.
NOTE 2 The word “heating” is used to refer to space heating.